MultiRanger/HydroRanger 100/200 Ultrasonic Level Controller
Brand: Siemens AGMultiRanger/HydroRanger is a versatile short- to medium-range ultrasonic single- and multi-vessel level monitor/controller for virtually any application in a wide range of industries.
MultiRanger/HydroRanger can be used on different materials, including fuel oil, municipal waste, acids, woodchips or on materials with high angles of repose.
Features- Differential Measurement And Six Control Relays
- Process Intelligence
- Range Of Models For Simple Level Measurement Or Pump Control To More Complex For Differential Level, Open Channel Measurement, Advanced Pump Control, Alarming, And Gate Control
- Auto False-Echo Suppression To Avoid False Echoes From Fixed Obstructions
- Intuitive Ease Of Use
Controller Type
Versions
Mounting, Enclosure Design
Mounting, Enclosure Design
Input Voltage
Number of Measurement Points
Number of Measurement Points
Data Communications (SmartLinx)
Output Relays
Approvals
Approvals
Additional Options
Stainless Steel Tag
View Details
Part Number / SKU
7ML5033-1AA00-1A -Z+Y15
Specifications
Brand
Measuring Range
- 0.3 to 15 m (1 to 50 ft)
- transducer dependent
Measuring Points
- 1 or 2
Input Analog
- 0-20 mA or 4-20 mA, from alternate device, scalable
Input Discrete
- 10-50 Vdc switching level Logical 0 < 0.5 Vdc Logical 1 = 10-50 Vdc max. 3 mA
Output EchoMaximum Transducer
- 44 kHz
Output Ultrasonic Transducer
- Compatible transducers: ST-H and EchoMax. series XPS-10, XPS-15/15F, and XRS-5
Relays
- Version with 1 relay (MultiRanger 100 only) 1 SPST Form A
- Version with 3 relays 2 SPST Form A/1 SPDT Form C
- Version with 6 relays 4 SPST Form A/2 SPDT Form C
- Model with 1 relay 1 SPST Form A
- Model with 3 relays 2 SPST Form A/1 SPDT Form C
- Model with 6 relays 4 SPST Form A/2 SPDT Form C
mA Output
- 0-20 mA or 4-20 mA
- Maximum load 750 ohms, isolated
- Resolution 0.1 % of Range
Error in Measurement
- 0.25 % of Range or 6 mm (0.24 inch), whichever is greater
- ± 4 mm (0.16 inch) in combination with an XRS-5 transducer on ranges 4 m (13 ft) or less
Resolution
- 0.1 % of Measuring Range or 2 mm (0.08 inch), whichever is greater
Temperature Compensation
- -50° to +150° C (-58° to +302° F)
- Integral temperature sensor
- External TS-3 temperature sensor (optional)
- Programmable fixed temperature values
Installation Conditions
- Location Indoor/outdoor
- Installation category II
- Pollution Degree 4
Ambient Conditions
- Ambient temperature (Housing) -20° to +50° C (-4° to +122° F)
- Storage temperature -20° to +50° C (-4° to +122° F)
Weight
- Wall Mount 1.37 kg (3.02 lb)
- Panel mount 1.50 kg (3.31 lb)
Material (Enclosure)
- Polycarbonate
Degree of Protection (Enclosure)
- Wall Mount IP65/Type 4X/NEMA 4X
- Panel mount IP54/Type 3/NEMA 3
Transducer and mA Output Signal
- 2-core Copper Conductor, twisted, shielded, 0.5 to 0.75 mm²
- (22 ... 18 AWG), Belden 8760 or equivalent is acceptable
Maximum Separation Between Transducer and Transceiver
- 365 m (1 200 ft)
Displays and Controls
- 100 x 40 mm (4 x 1.5 inch) multi-block LCD with backlighting
Programming
- Programming using hand-held programmer, SIMATIC PDM or via PC with Dolphin Plus software
Power Supply
- AC version 100 - 230 Vac ± 15 %, 50/60 Hz, 36 VA (17 W)
- DC version 12-30 Vdc (20 W)
Certificates & Approvals
- CE
- RCM
- EAC
- KCC
- FM
- CSAUS/C
- UL listed
- Lloyd’s Register of Shipping
- CSA Class I, Div. 2, Groups A, B, C, and D, Class II, Div. 2, Groups F and G, Class III (wall mount only), ATEX II 3D, EAC Ex
Communication
- RS-232 with Modbus RTU or ASCII via RJ-11 connector
- RS-485 with Modbus RTU or ASCII via terminal blocks
- Optional: SmartLinx cards for - PROFIBUS DP - DeviceNet
- Wet Wells
- Flumes/Weirs
- Bar Screen Control
- Hoppers
- Chemical Storage
- Liquid Storage
- Crusher Bins
- Dry Solids Storage