SITRANS TF - Temperature Transmitter In Field Enclosure
Brand: Siemens AGSITRANS TF is an IP67 field transmitter for heavy industrial use.
It transforms resistance thermometers, thermocouples, Ohm and mV signals into a load independent DC current corresponding to sensor characteristic or a digital signal according Fieldbus standard Profibus PA or Foundation Fieldbus.
Features- Flexible use - Local sensing of measured values over digital display; version without transmitter
- Rugged two-chamber enclosure in die-cast aluminum or stainless steel
- Easy handling - Test terminals for direct read-out of the output signal without breaking the current loop
- Unobstructed operation – remote mounted sensor prevents transmitter from heating up, immune against vibrations and oscillations thanks to long neck tubes and protection pipes
Specifications
Brand
Thermometer Input Type
- According to IEC 60751: Pt25 … Pt1000
- According to JIS C 1604, a = 0.00392 K-1: Pt25 … Pt1000
- According to IEC 60751: Ni25 … Ni1000
Thermometer Connection
- 2,3,4-Wire connection
Sensor Current
- ≤ 0.45 mA
Response Time
- ≤ 250 milliseconds for 1 sensor with break monitoring
Sensor Type
- Resistance-based, potentiometers
Thermocouple Type
- Type B, C, D, E, J, K, L, N, R, S, T, U
Output Signal
- 4 ... 20 mA, 2-Wire
Measuring Accuracy
- Error in the analog output (digital/analog converter): < 0.025 % of measuring span
Ambient Temperature
- -40° C to 85°
- -40° F to 185° F
Degrees of Protection
- IP66/67/68
Certifications & Approvals
- With digital display: II 2 (1) G Ex ib [ia Ga] IIC T4 Gb, II 2 G Ex ib IIC T4 Gb, II 2 D Ex ia IIIC T100° C Db
- Without digital display: II 2 (1) G Ex ib [ia Ga] IIC T6 Gb, II 2 G Ex ib IIC T6 Gb, II 2 D Ex ia IIIC T100° C Db
- IECEx
- EAC Ex(GOST)
- INMETRO
- NEPSI
- KOSHA
Protocol
- HART protocol, version 5.9
- SITRANS TF can be used everywhere where temperatures need to be measured under particularly adverse conditions, or where a convenient local display is ideal.